High Efficiency, Superior Model

Hitachi SET-FREE WS series central air conditioner combines inverter drive technology with water source heat working technology. All the features of the optimization design ensure a high COP value over a wider operating range in cooling and heating.

Simultaneous Cooling and Heating, More Energy Saving in Heat Recovery System

The need for simultaneous cooling and heating has emerged as a result of the increasing number of large modern buildings with their complex structures, functions and more comfort demands, especially in seasonal transitions or in winter months. In a conventional central air conditioning system, more energy is consumed when heating and cooling are carried out at the same time.

Model RAS-8 FSNYW1Q RAS-10 FSNYW1Q
Energy Supply V / Hz 3Φ,380~415V/50Hz, 380V/60Hz
Nominal Cooling Capacity*1 kW 22,40 28,00
Nominal Cooling Capacity*2 kW 25,00 31,50
IPLV (C) 5,60 5,65
External Dimensions Height mm 1000 1000
Width mm 780 780
Depth mm 550 550
Alan m² 0,43 0,43
Weight kg 160 160
Water Side Heat Exchanger Water Temperature*3 ºC 10-45 10-45
Water Flow l / min 76,8 96,0
Water Pressure Drop kPa 35 40
Sound Pressure Level*2 Cooling/Heating dB(A) 50 51
Piping Refrigerant Liquid Pipe Φmm Φ12,7 Φ12,7
Refrigerant Gas Pipe Φmm Φ 19,05 Φ22,2
Water pipe DN32 DN32
Connector Female G11 / 4B G11 / 4B
Drain Pipe DN15 DN15
Water Side Withstand Pressure kgf/cm 20 20
Max. Number of Connectable Indoor Units 13 16